Type | Index number | Status |
---|---|---|
Centralised MEV and MVHR systems | 500274 | Normal |
Brand | Model name | Model qualifier |
Manrose | MANHR4500DC2 | |
System type | balanced whole-house mechanical ventilation with heat recovery | |
Duct type | rigid | |
Minimum duct size | 125 mm diameter or 204 x 60 rectangular or larger | |
Original manufacturer name | Manrose Manufacturing Ltd | |
Current manufacturer name | Manrose Manufacturing Ltd | |
Manufacturer address |
1 Albion Close Slough Berkshire SL2 5DT |
|
Manufacturer phone | 01753 691399 | |
Manufacturer website | www.manrose.co.uk | |
First year of manufacture | 2011 | |
Final year of manufacture | current | |
Summer bypass | no | |
Integrated to exhaust air heat pump | No | |
Entry updated | 11/11/2015 10:34 |
K+n wet rooms | SFP (W/l/s) [2009] | Efficiency (%) [2009] | SFP (W/l/s) [2012] | Efficiency (%) [2012] | SFP (W/l/s) [10] | Efficiency (%) [10] |
---|---|---|---|---|---|---|
n = 1 | 0.61 | 91% | 0.67 | 90% | 0.67 | 90% |
n = 2 | 0.65 | 90% | 0.85 | 90% | 0.85 | 90% |
n = 3 | 0.76 | 89% | 1.09 | 87% | 1.09 | 87% |
n = 4 | 0.94 | 88% | 1.36 | 86% | 1.36 | 86% |
n = 5 | 1.11 | 87% | - | - | - | - |
Back to search results | Back to search | Back to all product types